2 MW natural gas generator (2,000 kW)
2 MW gas power: Weichai WPG1750 and WPG3500, Yuchai and Jichai units of 2,000–2,200 kW, or two smaller units. Continuous ratings and prices incl. VAT.

There is no single Weichai unit at exactly 2 MW: between the WPG1750 with 1,400 kW continuous and the WPG3500 with 2,800 kW there is a gap. Yuchai and Jichai have units rated at 2,000 and 2,200 kW.
This is not an excuse but the starting point: at this size the decision is the layout of an energy center, not one machine.
2 MW class
| Model | Power | Engine | Gas at full load | Open-frame price, incl. VAT |
|---|---|---|---|---|
| Weichai WPG1750 | 1,750 kW (1,400 continuous) | Baudouin 12M55G6N0/5 · 1,500 rpm | 360 m³/h | Price on request |
| Jichai 2000GF10-T | 2,000 kW | L20V190ZLT-2 · 1,000 rpm | ≈ 513 m³/h | 53,900,000 RUB≈ $656,100 |
| Yuchai YC16VCG-2000N5LC | 2,000 kW | YC16VC3300N-D30 · 1,500 rpm | 547.6 m³/h | 57,900,000 RUB≈ $704,800 |
| Jichai 2200GF-T | 2,200 kW | L20V200ZLT-2 · 1,000 rpm | ≈ 565 m³/h | 58,900,000 RUB≈ $717,000 |
| Weichai WPG3500 | 3,500 kW (2,800 continuous) | Baudouin 20M55G6N1/5 · 1,500 rpm | 649 m³/h | Price on request |
Prices are for the genset on an open frame, incl. VAT, excluding canopy, delivery and commissioning. ≈ $ at the Central Bank of Russia rate of 82.15 RUB/USD as of Nov 14, 2026. Contracts and payments in RUB.
1.5 MW and 4 MW
| Model | Power | Engine | Gas at full load | Open-frame price, incl. VAT |
|---|---|---|---|---|
| Yuchai YC16VCG-1500N5LC | 1,500 kW | YC16VC2470N-D30 · 1,500 rpm | 395 m³/h | 42,900,000 RUB≈ $522,200 |
| Weichai WPG1500 | 1,500 kW (1,200 continuous) | Baudouin 16M33G6N0/5 · 1,500 rpm | 310 m³/h | Price on request |
| Jichai 1600GF-T | 1,600 kW | L16V200ZLT-2 · 1,000 rpm | ≈ 419 m³/h | 44,900,000 RUB≈ $546,600 |
| Jichai 4000GF10-T | 4,000 kW | 16V26/32 · 1,000 rpm | ≈ 1,027 m³/h | Price on request |
What to look at
WPG1750 plus WPG625 give 1,900 kW continuous; WPG1750 plus WPG1000 give 2,070 kW. More expensive than one large unit, but the site keeps running while one is serviced.
Makes sense if the site will grow. An underloaded gas genset works worse: consumption per kWh rises and wear speeds up. A long-term load below half of rated power is bad for a gas engine.
Two megawatt-class units use 500–700 m³ of gas per hour. Confirm the volume and pressure at peak with the gas utility before ordering: approvals take longer than delivery.
At this size a grid connection often costs as much as own generation but takes much longer. That is usually why clients come to us.
Warranty on Weichai: 24 months or 8,000 operating hours; 60,000 operating hours to major overhaul; lead time 50–60 days for large units.
Related pages
Case studies and articles
Questions
Why can't the WPG1750 count as a 2 MW unit?
Because 1,750 is prime power; around the clock the unit gives 1,400 kW. The gap to 2 MW is 600 kW, almost a third of the plan: on a mining site that is about 170 machines that will not start.
One 2.8 MW unit or two 1.4 MW units?
One is cheaper in capital cost and simpler to connect. Two give redundancy and handle variable load better: at half load one unit runs at full power instead of two at half. A steady 24/7 load suits one unit; a site that grows in phases suits two.
How many ASICs can 2 MW run?
About 570 machines drawing 3.5 kW on average, with headroom for the site's auxiliary load: two mining containers of about 270 places.
How much space does a 2 MW energy center need?
Count service aisles and space for radiators and the gas train, not just the footprint of the gensets. Two megawatt-class units in containers with aisles need a plot of about 40 × 20 m. We lay it out on your site plan.