How to size a gas generator for an ASIC fleet

The most common mistake on a first mining site is to size the generator from the miners' nameplate power and buy a unit with no headroom. Here is how to size a gas generator set for an ASIC fleet properly, step by step.

Mining container with exhaust louvers and power cables at a FastMine site in the Saratov region
Mining & hosting
Topic
6 min
Reading time
Nov 3, 2026
Published in English
Key points
  • Use the real draw at the wall: hashrate × efficiency, about 3–3.6 kW per modern ASIC.
  • Add 5–8% for auxiliary load: ventilation, lighting, cooling and the genset's own controls.
  • Size on continuous power (COP), not prime power (PRP): mining is a flat 24/7 load.
  • Keep a 10–15% reserve, and consider two units instead of one for redundancy during maintenance.

Step 1. Calculate what the fleet actually draws

Take the real power draw at the wall, not the nameplate figure. For most current models it is 3–3.6 kW per machine. An Antminer S21 XP at 270 TH/s and 13.5 J/TH draws about 3.6 kW; a Whatsminer M60 at 156 TH/s and 19.9 J/TH draws about 3.1 kW. Power draw and break-even electricity rates for other models, including the Antminer S21 Pro+, are on our ASIC profitability pages.

The calculation is simple: hashrate times efficiency. 270 TH/s × 13.5 W per TH/s = 3,645 W. If your fleet is uniform, this exact figure, not "roughly three and a half kilowatts", goes into the sizing.

Step 2. Add the auxiliary load

This is the line people forget most often. Container ventilation, lighting, cooling and the genset's own controls add 5–8% on top of the miners. For a fleet of 200 machines that is 35–56 kW, the output of another small genset.

Step 3. Size on COP, not PRP

A genset datasheet gives two power ratings. PRP (prime power) is the maximum the unit delivers with time limits. COP (continuous power) is the rating for uninterrupted operation. Mining is a flat, round-the-clock load with no peaks and dips, so you size on COP.

ModelContinuous (COP)Prime (PRP)ASICs on COP
Weichai WPG312200 kW250 kWup to 57
Weichai WPG500320 kW400 kWup to 91
Weichai WPG625500 kW625 kWup to 142
Weichai WPG1000670 kW800 kWup to 191
Weichai WPG13751,100 kW1,375 kWup to 314

At 3.5 kW per machine. For hydro-cooled models such as the Antminer S23 Hyd the draw per unit is higher; size on your own configuration.

Gas generator sets next to mining containers at a FastMine site in the Saratov region, aerial view
Gensets and mining containers side by side at one of our sites in the Saratov region.

Step 4. Keep a reserve

Running a genset at its limit means higher gas consumption and a shorter life to major overhaul. A normal reserve is 10–15%. In practice we load a 320 kW continuous unit (the Weichai WPG500, 400 kW prime / 320 kW continuous) with about 80 machines, although the COP arithmetic allows 91. The difference is that reserve.

Step 5. One unit or two?

One large unit is cheaper per kW and simpler to connect. Two smaller ones give redundancy: during scheduled maintenance the site keeps running at half power instead of stopping completely. The service interval on the Weichai WPG312 and WPG500 is 500 operating hours, which is roughly every 3 weeks at 24/7 operation.

This is why our clients' sites in the Vologda and Yaroslavl regions run two 400 kW units each, and the Samara and Vyksa sites three, rather than one larger machine. The units run in parallel through their controllers. See the Yaroslavl case study and the Vyksa mining site: three 400 kW units, a 40 ft container and about 220 ASICs sized to 960 kW of continuous power.

If you would rather not run your own generation, you can host ASICs on ours: see gas-powered Bitcoin mining at our sites in the Saratov region.

What to check before you order

  1. Gas volume and pressure on site. At one megawatt this, not the choice of genset, becomes the main constraint.
  2. Where the exhaust goes and how cooling air is supplied and removed.
  3. The foundation and access roads for unloading.
  4. Lead time: the WPG312 and WPG500 ship in 30 days, larger models in 50–60 days.

A full checklist is in what you need to install a gas generator set.

Gas generator sets for Bitcoin miningSend us your ASIC list and the gas data for your site. We will size the plant, calculate gas consumption and give you lead times.Gensets for mining

Frequently asked questions

How many ASIC miners can a 400 kW gas generator run?

A Weichai WPG500 is 400 kW prime and 320 kW continuous. At 3.5 kW per miner, continuous power covers up to 91 machines; with a normal reserve we plan about 80.

Should I size a generator for mining on prime or continuous power?

On continuous power (COP). Mining is a flat 24/7 load, and running on prime power around the clock raises gas consumption and shortens engine life.

How much auxiliary load should I add?

5–8% on top of the miners' draw for ventilation, lighting, cooling and the genset's controls, then a 10–15% reserve.

Read next

This article is an English adaptation of our Russian original (Jul 29, 2026), rewritten for international readers. Prices are in RUB incl. VAT for supply in Russia; USD amounts are for reference only. Contracts are signed with TDM LLC (INN 9726051386) under Russian law, in RUB. Figures are estimates, not a public offer or a guarantee of income.